Energy consumption in buildings is heavily affected by climate change. It causes significant variations of the outdoor design conditions, cooling and heating loads. In this paper, a total of 40 years (1967-2006) of hourly temperature data were considered in four decades and outdoor design conditions for each decade were calculated. It was found that wet-bulb temperature (WBT) has increased by 3.28 degrees C during the mentioned period, which impacts on design and selection of the cooling equipment. The results show that cooling hours is projected to increase around 15% over the whole 1967-2006 period. The most important result found in this study is the inability of direct evaporative cooling (DEC) systems in preparing comfort condition after 1997, whereas these systems provided thermal comfort in Tehran's buildings from 1967 to 1996. The prediction of climate change impacts on the outdoor design conditions and cooling systems performance until 2020 demonstrates dry bulb temperature (DBT) and WBT increase 1.05 degrees C and 2.42 degrees C respectively. Hence, indirect-direct evaporative cooling systems (IDEC) may not be responsible for the years after 2016. Besides, the additional energy for absorption and vapor compression (VC) cooling systems will grow quickly in the future.