An investigation on spray cooling using saline water with experimental verification

作者:Sadafi M H*; Ruiz S Gonzalez; Vetrano M R; Jahn I; van Beeck J; Buchlin J M; Hooman K
来源:Energy Conversion and Management, 2016, 108: 336-347.
DOI:10.1016/j.enconman.2015.11.025

摘要

A natural draft dry cooling tower rejects heat in a power plant. Spray cooling of the inlet air to the cooling tower improves the total efficiency of the power plant. To overcome the scarcity of natural water sources, this research is studying the usage of saline water in spray assisted dry cooling towers. A nozzle is analysed experimentally. It is shown that the CFD model captures the spray well. A full cone spray is simulated in a vertical cylindrical domain representative of cooling tower flows. To investigate the influences of initial and ambient conditions on the spray performance, fourteen different cases are simulated and trends analysed. It is shown that the distances from the nozzle, after which the dry stream starts (wet lengths), are in the range of 4.3-5.25 m depending on the test conditions. A dimensionless study is performed on the wet length and cooling efficiency as the two main parameters. Finally, to predict the wet length and cooling efficiency, two dimensionless correlations are presented and their impact on cooling tower operation is discussed.

  • 出版日期2016-1-15