Analysis and Measures of Ultralow-Frequency Oscillations in a Large-Scale Hydropower Transmission System

作者:Mo, Weike; Chen, Yiping; Chen, Haoyong*; Liu, Yingshang; Zhang, Yong; Hou, Jun; Gao, Qin; Li, Chongtao
来源:IEEE Journal of Emerging and Selected Topics in Power Electronics, 2018, 6(3): 1077-1085.
DOI:10.1109/JESTPE.2017.2759810

摘要

The Yunnan power grid has a large-scale hydropower station, whereby the power generated at the station is transmitted via HVdc lines under an asynchronous operation mode. In the system performance test of the Yunnan asynchronous operation, a 0.05-Hz ultralow-frequency oscillation occurred in the grid. This ultralow-frequency oscillation is a frequency stability problem caused by instability of hydraulic turbine governing system, which is quite common in the islanded system and very rare in the normal synchronous system. The relationship between the speed governing system stability of one unit and that of the system with parallel operation units was proposed to explain that the high proportion of units with an unstable governing system will lead to system frequency instability and the reduction in loads in the traditional sense was proven to further worsen the frequency stability of the Yunnan asynchronous system. By using related measures, the ultralow-frequency oscillation of the Yunnan asynchronous system has been curbed effectively. System performance testing verified the effectiveness of the analysis and the measures.