The amount of distributed energy resources (DERs) has increased constantly worldwide. The power ratings of DERs have become considerably high, as required by the new grid code requirement. To follow the grid code and optimize the function of grid-connected inverters based on DERs, a phase-locked loop (PLL) is essential for detecting the grid phase angle accurately when the grid voltage is polluted by harmonics and imbalance. This paper proposes a novel low-pass notch filter PLL (LPN-PLL) control strategy to synchronize with the true phase angle of the grid instead of using a conventional synchronous reference frame PLL (SRF-PLL), which requires a d-q-axis transformation of three-phase voltage and a proportional-integral controller. The proposed LPN-PLL is an upgraded version of the PLL method using the fast Fourier transform concept (FFT-PLL) which is robust to the harmonics and imbalance of the grid voltage. The proposed PLL algorithm was compared with conventional SRF-PLL and FFT-PLL and was implemented digitally using a digital signal processor TMS320F28335. A 10-kW three-phase grid-connected inverter was set, and a verification experiment was performed, showing the high performance and robustness of the proposal under low-voltage ride-through operation.