摘要

This paper presents a new algorithm for the prediction of indoor suspension particle dispersion based on a v(2)-f model. In order to handle the near-wall turbulence anisotropy properly, which is significant in the dispersion of fine particles, the particle eddy diffusivity calculated using different formulae among regions of the turbulent core and in the vicinity of walls. The new algorithm is validated by several cases performed in two ventilation rooms with various air distribution patterns. The simulation results reveal that v(2)-f non-linear turbulence model combined with a particle convective equation gives satisfaction agreement with the experimental data. It is generally found that the dynamic equation combined with the v(2)-f model can properly handle low Reynolds number (LRN) flow which are usually encountered in indoor air flows and fine particle dispersion.