摘要

This article presents relevance vector machine (RVM) based relaying scheme for busbar protection which correctly differentiates between internal faults on busbar and external faults. To validate the proposed scheme, numerous computer simulations have been carried out on an existing 220 kV Indian power generating station having different types of bays such as line, transformer, reactor & generator with generator transformer (GT). Various fault conditions (test data set of 23,760) have been simulating using the power system computer aided design (PSCAD)/ electromagnetic transient direct current (EMTDC) software package (Winnipeg, MB, Canada) by varying fault & system parameters. The proposed RVM based fault discrimination scheme is executed in MATLAB software (The Math- Works, Natick, Massachusetts, USA) by loading the simulation data. Comparative evaluation of the proposed RVM based scheme with the existing support vector machine (SVM) based scheme clearly indicates the superiority of the proposed scheme in terms of decision speed (faster than SVM based scheme) and classification accuracy (more than 99%). Moreover, it does not operate under different types of external faults and system disturbances. Subsequently, the proposed scheme remains stable during severe current transformer (CT) saturation condition.