摘要

This paper presents a numerical study of a steam ejector using CFD with the objective of identifying suitable experimental conditions that allows for a reliable ejector cycle operation. The flow structure and the mixing process inside the ejector were assessed for a range of operating conditions typical for a solar driven air conditioning system. The effect of varying the condenser pressure was studied. It was found that for relatively low condenser pressures (%26lt;2.5 kPa), two distinct shock waves occurred in the diffuser section resulting in a reduced recompression efficiency, although it did not have a direct impact on the entrainment ratio. The effect of generator pressure was also studied. It was found that the entrainment ratio showed a maximum for constant condenser conditions. A near optimal condition of 70 kPa generator and 3 kPa condenser pressures were identified and tested in a preliminary experiment carried out with the solar driven ejector system installed in Tunis. 2013 Elsevier Ltd and IIR.

  • 出版日期2014-3