摘要

The SOC(Self-Organized Criticality) characteristics of distribution network power-supply failure can be researched based on the statistics of power-supply reliability, which may provide the theoretical basis for improving the operational level and power-supply reliability of distribution network. Based on the power-supply reliability data of Guangzhou 10 kV distribution network, the quantity of de-energized household and the duration of emergency outage are chosen as the statistical objects. The linear relationship between the scale and frequency of the chosen objects on log-log scale is fitted by the least squares method and validated by F-test, which preliminarily verifies the SOC characteristics of 10 kV distribution network power-supply failure. The operational significance of SOC characteristics to the operation of distribution network is given.