Detection of Fouling in a Cross-Flow Heat Exchanger Using Wavelets

作者:Ingimundardottir Helga; Lalot Sylvain*
来源:Heat Transfer Engineering, 2011, 32(3-4): 349-357.
DOI:10.1080/01457632.2010.495668

摘要

Detection of fouling in a heat exchanger experiencing perfect steady-state conditions is not very difficult. But the challenge is to detect fouling when all inputs (inlet temperature of the fluids and the mass flow rates) are simultaneously varying. In this paper it has been considered that the mass flow rates can vary in a ratio of 2, and that the inlet temperatures can vary by about +/- 20%. This first approach is dedicated to show the feasibility of using the wavelet transform. It has been considered that getting simulated data is the best way. In fact, it is then possible to introduce an arbitrary fouling factor. Thus, in the first part of the paper the model of the heat exchanger is presented. It is developed using Simulink. The validation is carried out on an electrical heater, for which it is possible to find an analytical solution for transient states. It is also shown that steady states are accurately computed over a large range of the number of transfer units and heat capacity rate ratios. Then a brief overview of the wavelet transform is given. Then basic examples show that the wavelet transform can help to find the trend of time series. It is then applied to the analysis of the "wavelet-transformed" effectiveness of the heat exchanger. This analysis is carried out on a sliding observation window (to be able to detect fouling on-line). It is shown that fouling is detected at a very early stage.

  • 出版日期2011