摘要

The complicated fault current characteristics of doubly-fed induction generator (DFIG) deteriorate the performance of the conventional superimposed phase selectors when they are applied on the interconnection line of DFIG-based wind farm, which is difficult to satisfy the requirement of phase selection of interconnection line protection of DFIG-based wind farm and reclosing. Based on it, the defects of the traditional phase selectors applied on the interconnection line of DFIG-based wind farm are analyzed according to the low voltage ride through control strategy of DFIG. Then, a new fault phase selector is proposed based on the comparison of superimposed amplitude between phase voltage and line voltage. The selection coefficient of fault phase is established based on the proportional relation of superimposed amplitude between phase voltage and line voltage at the relay location of DFIG-based wind farm. According to the characteristics of the fault phase selection coefficient under different fault conditions, the fault phase selection can be realized. A variety of simulation cases show that the performance of the proposed fault phase selection method is much better than that of conventional method which can select the fault phase effectively.