摘要

This paper presents the study, analysis, and practical implementation of a versatile unified power quality conditioner (UPQC), which can be connected in both three-phase three-wire (3P3W) or three-phase four-wire distribution systems for performing the series-parallel power-line conditioning. Thus, even when only a 3P3W power system is available at a plant site, the UPQC is able to carry out power-line compensation for installed loads that require a neutral conductor to operate. Different from the control strategies used in the most of UPQC applications in which the controlled quantities are nonsinusoidal, this UPQC employs a dual compensation strategy such that the controlled quantities are always sinusoidal. Thereby, the series converter is controlled to act as a sinusoidal current source, whereas the parallel converter operates as a sinusoidal voltage source. Thus, because the controlled quantities are sinusoidal, it is possible to reduce the complexity of the algorithms used to calculate the compensation references. Therefore, since the voltage and current controllers are implemented into the synchronous reference frame, their control references are continuous, decreasing the steady-state errors when traditional proportional-integral controllers are employed. Static and dynamic performances, as well as the effectiveness, of the dual UPQC are evaluated by means of experimental results.

  • 出版日期2016-8