摘要

An adaptive control of DPWM implementable in clamped-three-level inverters with two strings of photovoltaic (PV) panels in cascaded connection is proposed in this paper. The proposed modulation is developed based on the so-called circuit-level decoupling concept. It is able to provide balance line voltage even under unbalanced dc links. The unequal dc voltages appeared due to asymmetric maximum point of power trackings (MPPTs) are controlled by proper injection of zero-sequence voltage to the common mode voltage, while the total dc voltage is regulated based on the voltage commands generated by the MPPT of each string. Thus, both PV strings are able to be operated based on their MPPTs while there is almost no low-order harmonic distortion at the inverter output current. Compared with the previous methods, the high capability of the proposed method is evaluated by simulation study and experimental tests.