In some situations, utilities may try to %26quot;save%26quot; the fuse of a circuit following temporary faults by de-energizing the line with the fast operation of an upstream recloser before the fuse is damaged. This fuse-saving practice is accomplished through proper time coordination between a recloser and a fuse. However, the installation of distributed generation (DG) into distribution networks may affect this coordination due to additional fault current contributions from the distributed resources. This phenomenon of recloser-fuse miscoordination is investigated in this paper with the help of a typical network that employs fuse saving. The limitations of a recloser equipped with time and instantaneous overcurrent elements with respect to fuse savings, in the presence of DG, are discussed. An adaptive relaying strategy is proposed to ensure fuse savings in the new scenario even in the worst fault conditions. The simulation results obtained by adaptively changing relay settings in response to changing DG configurations confirm that the settings selected theoretically in accordance with the proposed strategy hold well in operation.