In this paper the multiconductor cell analysis (MCA) has been applied to Milliken type cables of large cross-section over 1600 mm(2). Since IEC 60287-1-1 does not provide values for the calculations of skin and proximity effects for these cases, these procedures become important to foresee skin effect values in the planning phase, where measurements are not possible. In order to develop a programmable procedure, an idealized M-type core with six sectors has been developed. It is composed of cylindrical wires inscribed on a hexagonal grid: it allows investigating the skin effect phenomena in many cross-sections (in the range 1600-2500 mm(2)) without being constrained by the manufacturer techniques. The effects of lack of insulation between the wires have been also analysed. Comparisons with some measurements reported in technical literature show a good agreement.