Ultra-saturation phenomenon is one of the false trips of the power transformer differential protection during unload transformer energization with additional line/load from the supplying side. This article presents, at first, a new model for investigating the ultra-saturation phenomenon during unload power transformer energization with additional line/load from the supplying side and considers its effect on the differential protection of the power transformer. In this model, the non-linear characteristic of the power transformer core and the effect of current transformer are taken into account. It is assumed that the additional line/load from the supplying side of the power transformer is a resistive and an inductive load. Also, the effect of the residual flux, inception angle, and additional line/load from the supplying side on the ultra-saturation phenomenon is investigated.