摘要

Some problems exist in travelling wave transient process of HVDC transmission line, such as chromatic dispersion attenuation and bipolar coupling, making it difficult to analyze fault quantities. In addition, protection device sampling is stochastic, further increasing difficulty of quantitative analysis of criterion characteristic parameters. Therefore, a unified and effective setting method is absent in travelling wave protection. This paper analyzed demand of travelling wave setting from perspective of selectivity and sensitivity, and established a fault quantity analytical model for setting calculation based on key fault locations. In order to eliminate protection sampling randomness, an analytical calculation method of criterion characteristic parameters was proposed. According to characteristic curve demonstrating characteristic parameterchanges due to transition resistances and lightning disturbances, protection setting was calculated. This setting has extraordinary ability against transition resistance and lightning disturbance. Comparative analysisof protection setting of actual HVDC transmission line and protection boundary verified validity of the proposed analytical setting method.