The aim of this paper is focused on the energy performance of buildings containing massive wall alternatives. The analysis comprised the comparison of the heating and cooling loads of seven characteristic wall configurations of one sample building with different dynamic internal heat capacity (ISO 13790:2008) in spite of the equal thermal resistance. The equal thermal resistance, as derived from simple steady-state condition, was imposed in order to allow research of effects solely attributed to the wall heat capacity on the building performance. A detached one floor dwelling exposed to different climate conditions in Portugal was analysed to illustrate the effect of the same wall in terms of energy demand during cold and hot weather conditions. A whole building dynamic modelling using EnergyPlus was employed for the energy analysis. The best thermal performance was obtained with massive walls that were located at the inner side, for a very heavy weight building and high building time constant.