摘要

In order to increase cooling or heating efficiency, a porous computational fluid dynamics (CFD) model is employed to predict the thermo-fluid status and optimize the placement of outdoor units. A full scale model is established to validate the accuracy of CFD simulation in terms of velocity and temperature distributions. The comparison between the measurement and the simulation shows a good agreement. By evaluating the condensers'; sucked air temperature with CFD for three units installed in a row, it is found that the minimum separation distance among neighboring units is 0.2 m; a vertical wall should be apart from the unit line by at least 0.8 m; and large different operating pressures among units do not impact the flow rate and the heat transfer of the other units meaningfully. ? right.

  • 出版日期2010