摘要

This paper proposes a communication-assisted fault localization, isolation, and restoration method for microgrids based on a multi-agent system. The proposed system comprises distributed agents, located in the middle and at the two ends of a protection section, which will detect a fault through phase angle comparison of current signals at both sides of a given distribution line. The agents then send trips signal to corresponding circuit breakers accordingly. The importance of the proposed protection technique is twofold. First, it eliminates the use of voltage transformers and thus reduces costs. Second, it does not require transfer of data along long distances, which decreases the delay time for fault isolation. Power restoration processes following the fault clearance considering voltage, frequency, and power flow constraints in the microgrid under study were also performed. Simulation of the proposed protection methodology was presented followed by experimental verification. The experimental results showed excellent agreement with the simulated protection scheme.

  • 出版日期2017-6