Accidental contamination of a German town's drinking water with sodium hydroxide

作者:Lendowski Luba*; Faerber Harald; Holy Andreas; Darius Anke; Ehrich Bernd; Wippermann Christine; Kuefner Bernd; Exner Martin
来源:International Journal of Hygiene and Environmental Health, 2015, 218(3): 366-369.
DOI:10.1016/j.ijheh.2015.01.006

摘要

Case report of a very serious drinking water incident putting up to 50,000 inhabitants of a town near Bonn in North Rhine-Westphalia, Germany at risk. A concentrated solution of highly alkaline water by sodium hydroxide was accidentally washed into the town's drinking water at a pumping station and increased the pH-value of the water to 12. Residents who came into contact with the contaminated water immediately had a toxic reaction. The incident was detected by complaints from customers and after that was stopped within several hours. The pipes were flushed and the customers were warned not to use the water till the all clear. After this immediate management there was an investigation and the cause of the incident was detected as an accidental release of accumulated sodium hydroxide (NaOH) solution. The lack of a network alarm system and the automatic cut-off mechanisms as deficiencies in the design of the station were rectified by the water company immediately after the incident.