Restorative self-healing is one of the most important features of smart grids. The major purpose of a restorative self-healing control strategy is to steer a power system to secure operating states. In this paper, a self-healing transmission network reconfiguration algorithm based on the complex network theory is proposed. The capacities of generators and the amounts of important loads (i.e., the high priority loads), as well as the distribution and importance of each transmission line in the outage area are considered in the proposed method using the presented electrical "betweenness." Next, the optimal restoration paths and the optimal restorative self-healing strategy can be attained automatically. Finally, the New England 10-unit 39-bus system and a part of the actual Guangdong power system in China are employed to illustrate the features of the proposed method.