In this paper, a novel distance protection algorithm for improving properties of relay in high resistance to ground fault was presented. This algorithm deduces a linear differential equation with three unknown quantities. The core idea of this algorithm is to regard the system after fault point as an inductance and the equation is inferred from accurate fault equation. Theoretical analysis and simulation results prove it applicable to short and mid-range transmission lines, also the bearing ability to high resistance fault and high accuracy of this algorithm, especially in the end of protection domain, which prevent the overreach happening. This algorithm is hoped to resolve the effect of fault resistance to distance protection and be a new and fast distance protection.