Anti-Islanding Protection Relay for Medium Voltage Feeder With Multiple Distributed Generators

作者:Xiao, Hua F.*; Fang, Zhijian; Xu, Dewei; Venkatesh, Bala; Singh, Birendra
来源:IEEE Transactions on Industrial Electronics, 2017, 64(10): 7874-7885.
DOI:10.1109/TIE.2017.2694394

摘要

Large distributed generators (DGs) are usually connected to medium voltage (MV, typically up to 50 kV) feeders directly. Their anti-islanding protections mainly rely on transfer trips from upstream substations through communication media, which are expensive and time-consuming because of infrastructure. This paper presents a local anti-islanding protection relay (LPR) as an alternative for the traditional transfer trip in MV feeder applications. The basic idea of the proposed LPR is to short phase to neutral or phase to phase voltages by thyristors at the point of common coupling (PCC) of each DG when either of them is crossing zero; then both variations of the thyristor current and voltage harmonic distortion at the PCC are observed and measured, and they are able to indicate the operating mode of the DG unit in either grid-connected or islanding. Further, this approach is analyzed and discussed based on a single DG scenario and a complicated scenario with two DGs and one shunt capacitor bank. Finally, a lot of experiment results with different scenarios are obtained based on a scale-down testing platform, which has been built in our lab by using per-unit method from an actual MV feeder system.