摘要

From the study of dispatcher power flow in a distributed energy management system (DEMS) among multiple control centers, a fixed-point iteration scheme for boundary bus states is constructed to modify the exterior network equivalent through data exchange. Implementation details such as determination of combination parameters, independent choice of reference bus, and distribution of unbalanced power are analyzed. Using this method, each subsystem involved in distributed computing can maintain its method of modeling the exterior network. Adverse effects of communication interference on computing can also be eliminated. Results consistent with integrated power flow are obtained with little loss of accuracy. Thus, the proposed algorithm is especially suitable for application in DEMS, in which control centers can only communicate by WAN. Tests are conducted on the IEEE 118-bus system partitioned into five subsystems, the IEEE 300-bus system, and an actual power system, which verifies the favorable convergence and effectiveness of the method.