摘要

A dynamic network reconfiguration methodology considering time-varying weather conditions is proposed. The aim of the proposed methodology is to minimize outage risk. To fully reflect actual weather severity, a classification method for weather states based on weather variables analysis is presented. Considering time-varying nature of weather, an approach to determine the optimal time for reconfiguration by comparing reliability change between adjacent intervals is provided. Then, applying the Quantum Genetic Algorithm to solve reconfiguration optimization problem is introduced. Simulation results on the IEEE 33-node test systems show that the proposed dynamic reconfiguration method can reduce distribution network's outage risk. In addition, weather conditions have impacts on outage risk of distribution network and should be considered in reconfirmation problems.