A multi-storey building with great diversity of room use was monitored after extensive renovation to remove mould growth secondary to a leaky roof. Tests for volatile organic compounds (VOC) with activated charcoal showed a successfully renovation. Solid phase microextraction (SPME) for detection of selected very volatile organic compounds (VVOCs) revealed indoor air concentrations ranging from 550 to 4600 mu g m(-3). The SPME technique also successfully detected emissions from working and building materials and documented the results of remedial measures in offices. The prior and current use of acetone, methyl acetate and 2-methylpentane within the building resulted in their elevated concentrations in other building floors.