摘要

In this paper, a method for fault locating in HVDC transmission lines is proposed which only uses the voltage signal measured at one of the line terminals. The postfault voltage signal, in a relatively short-time window, is considered and the corresponding fault location is estimated based on the similarity of the captured voltage signal to existing patterns. In this approach, the Pearson correlation coefficient is used to measure the similarity. Despite simplicity and low complexity of the proposed fault-location method, it does not suffer from the technical problems which are associated with the traveling-wave-based methods, such as the difficulty of identifying traveling wavefronts or the strong dependency of accuracy on the sampling frequency. Numerous training and test patterns are obtained by simulating various fault types in a long overhead HVDC transmission line under different fault location, fault resistance, and prefault current values. The accuracy of the proposed fault-location method is verified using these patterns.

  • 出版日期2013-10