Mechanism of ±800 kV HVDC converter abnormal block fault caused by lightning transient

作者:Zhang, Xiao*; Yu, Zhanqing; He, Jinliang; Zhang, Bo; Zeng, Rong; Jiang, Yukuan; Luo, Bin; Cai, Hansheng; Luo, Wei
来源:Electric Power Systems Research, 2014, 113: 157-164.
DOI:10.1016/j.epsr.2014.03.023

摘要

Abnormal bipolar block accidents caused by single-pole DC line lightning strikes happened several times in the Yunnan-Guangdong +/- 800 kV UHVDC system in South China, which are serious threats to system security. In this paper, the lightning transients in the primary and secondary circuits of both faulted and sound poles in UHVDC system are studied, in order to reveal the mechanism of such accidents. Wide-band circuit models of major UHVDC equipment are developed for simulations. Characteristics of intruding lightning surges and DC filter transient currents on both poles are analyzed, while interferences coupled into secondary cables under different loads and sheath grounding conditions are calculated. The cause of the abnormal block of the sound pole is recognized and explained. Finally, countermeasures are proposed to prevent the recurrence of similar unintended events and to improve the interference immunity of UHVDC system.