摘要

The coefficient of performance is one important evaluating indicator in the urban sewage heat pump system. Based on the engineering thermodynamics principle, the heating operating performance of direct and indirect systems was analyzed and compared. The results indicate that the actual COP of direct sewage source heat pump system is higher approximately 0.3 than that of indirect system, and the sewage temperature and the user supply water temperature have great influence on the system performance, while the temperature differences of sewage, intermediary water, the evaporator or the condenser has little influence.